AS 1940 bund calculator
How much your bund needs to hold for the fuel tanks inside it, whether a proposed bund holds enough, and the wall height a footprint needs.
Result
Send these figures to a sales engineer covering your state. We reply within 2 business days.
Send these specs for a quoteHow the calculator works
- Largest tank is the biggest single tank capacity you entered. Total stored adds up every tank.
- Bund must hold is 110% of the largest tank. Since the 2017 edition of AS 1940, a bund generally needs to hold at least that much. 1 m³ is 1,000L.
- Your bund holds is the internal length multiplied by the width and the wall height, less the space the other tanks, plinths and supports take up below the wall height.
- Wall height needed is what the bund must hold plus that space, divided by the internal length and width, rounded up to the next centimetre.
The calculator does not work out separation distances. They depend on the class and quantity of liquid stored, so check the standard or ask your consultant.
This calculator is general information only, not compliance advice. Councils, state dangerous goods regulators and insurers may have their own requirements. Your engineer and the site's approvals set the final design.
Diesel and petrol under AS 1940
AS 1940:2017, with Amendments 1 and 2, is the Australian Standard for the storage and handling of flammable and combustible liquids.
- Diesel is a Class C1 combustible liquid, because its flash point is above 60°C and no higher than 93°C.
- Petrol is a flammable liquid and needs larger separation distances than diesel.
- Self-bunded tanks are double wall. The outer wall is the containment, so there is no separate concrete bund to build. Ours hold up to 55,000L of petrol or up to 110,000L of diesel, and can be relocated (recertify the tank to keep the warranty). See our self-bunded fuel tanks.
- Fireguard® 4-hour tanks can reduce separation distances by as much as 50%. See our Fireguard® tanks.