How a tank inside a tank contains a leak and shows it, which of our underground and above-ground tanks are built this way, and when a single-wall tank is enough.

Get a price

Tell us roughly what you need. A sales engineer for your state replies within 2 business days.

Have drawings or a full spec? Use the detailed quote form, or call NSW +61 2 4964 8270 or WA +61 8 9434 1707.

By sending you agree to our Privacy Policy.

What a double-wall tank is

A double-wall tank has a primary wall that holds the fuel and a secondary wall around it. The gap between the two is the interstitial space.

If the primary wall ever leaks, the outer wall holds the fuel in the interstitial space instead of letting it reach soil, drains or groundwater. Monitoring that space shows the leak.

We build double-wall tanks in fibreglass (FRP), in steel, and in Glasteel® II, which puts a steel tank inside an FRP outer wall.

Two double-wall fibreglass fuel tanks in a lined excavation with install crew
Two double-wall fibreglass fuel tanks in a lined excavation with install crew

Why choose double wall

A single-wall tank relies on one wall, plus a bund above ground. A double-wall tank carries its own containment, and lets you check it.

360° secondary containment

On double-wall FRP the outer wall completely surrounds the primary wall, so a leak is held in the tank instead of reaching groundwater.

Leaks you can see

Where the interstitial space is monitored, a leak in the primary wall shows up before product reaches the ground.

No civil bund above ground

On a self-bunded tank the outer steel wall is the bund. There is no concrete bund to build and no rainwater to catch and dispose of.

Relocatable

Self-bunded and Fireguard® 4-hour tanks are self-contained, so they can be moved as the site changes. A relocated self-bunded tank needs recertifying to keep the warranty.

Meets containment rules

AS 4897 calls for secondary containment on underground petroleum storage systems. Under AS 1940 a bund generally needs to hold at least 110% of the largest tank, and on a self-bunded tank the outer wall is that containment.

A path for older sites

If your site still runs an older single-wall steel tank, a double-wall replacement adds secondary containment and leak monitoring.

Double-wall construction across our range

The idea is the same in each tank. The materials, the monitoring and where the tank goes are what change.

TankInstalledInner wallOuter wallLeak monitoring
Double-wall FRPUndergroundFRP with integral ribsFRP, full 360°Truchek® hydrostatic
Glasteel® IIUndergroundWelded mild steelFRP, fully enclosing the steelFactory-fitted vacuum gauge
Self-bundedAbove-groundSteelSteel wrap bundSee datasheet
Fireguard® 4-hourAbove-groundSteelSteel, with insulation between the wallsSee datasheet
Flameshield® 2-hourAbove-groundSteelSteelInterstitial monitoring

Underground

  • Double-wall FRP is fibreglass inside and out, from 2,000L to 150,000L, with 1 to 4 compartments. Fibreglass doesn’t rust, inside or out.
  • Glasteel® II puts a welded steel tank inside an FRP outer wall, so the steel never touches soil or groundwater and needs no cathodic protection. See how Glasteel® II works.
  • Both are installed by an accredited installer.

Above-ground

  • Self-bunded tanks hold up to 110,000L of diesel or 55,000L of petrol per tank, with no concrete bund.
  • Fireguard® adds insulation between the walls and is rated to the SwRI 4-hour fire test. See how fire-rated tanks work.
  • Flameshield® is accredited to a 2-hour fire test and comes horizontal or vertical, cylindrical or rectangular.

Interstitial monitoring

Containment holds a leak. Monitoring tells you it happened. Our underground tanks use two methods.

Hydrostatic, on double-wall FRP

Truchek® keeps the interstitial space filled with brine, and a reservoir on top of the tank holds it at a set level. It gives continuous leak detection, lets the owner do a visual tank tightness test and meets EPA requirements. See how Truchek® works.

Vacuum, on Glasteel® II

The interstitial space is put under vacuum at the factory and fitted with a vacuum gauge. A break in the inner or outer wall causes a loss of vacuum, so a regular check of the gauge confirms the tank’s integrity.

When single wall is enough

Underground, where secondary containment isn’t needed, such as water or some AdBlue installs, a single-wall FRP tank is lighter, delivered complete and quick to install.

Above ground, a single-wall horizontal tank sits in a simple concrete bund. It suits fuel farms and sites with an existing bund, at up to 150,000L per tank, with tanks side by side and manifolded.

Standards

AS 4897Underground petroleum storage systems, including secondary containment
AS 1940Storage and handling of flammable and combustible liquids, including bunding. See our AS 1940 guide
AS 1692Steel tanks: Glasteel® II, self-bunded and Flameshield® 2-hour
UL 1316Fibreglass underground tanks: double-wall FRP
UL 58Steel underground tanks: Glasteel® II
UL 142Steel above-ground tanks: Flameshield® 2-hour

General information only, not legal advice. Your state EPA or regulator and your site engineer set what applies to your site.

Our double-wall tanks

Each product page has sizes, construction details, datasheets and a quote form.

Tank Solutions – Fuel

Double-wall fibreglass fuel tanks

Double-wall FRP tank with 360-degree secondary containment.

Capacity
2,000–150,000L
Standard
UL 1316
Compatible media
Petrol, diesel, alcohols and alcohol–petrol blends
Tank Solutions – Fuel

Glasteel® II underground fuel tanks

A welded mild steel tank with an FRP outer layer that provides secondary containment, leak protection and corrosion resistance.

Capacity
2,000–200,000L
Standard
STI Glasteel® II licence
Compatible media
Fuels including blended fuels, ethanol and biodiesel
Tank Solutions – Fuel

Self-bunded diesel & fuel tanks

Relocatable double-wall steel tank that needs no on-site bund.

Capacity
Up to 55,000L petrol; up to 110,000L diesel
Standard
AS 1940, AS 1692
Compatible media
Diesel, unleaded petrol (ULP) and other Class 3 liquids
Tank Solutions – Fuel

Fireguard® 4-hour fire-rated tanks

Insulated double-wall steel tank rated to the SwRI 4-hour fire test.

Capacity
On request
Standard
STI Fireguard®
Compatible media
Fuels and other flammable and combustible liquids
Tank Solutions – Fuel

Service station fuel tanks

Double-wall FRP underground fuel tanks for new service stations, upgrades and replacements, with full 360-degree secondary containment.

Capacity
Up to 150,000L
Standard
UL 1316
Compatible media
Petroleum fuels, alcohols and alcohol-gasoline blends
Tank Solutions – Fuel

Flameshield® 2-hour fire-rated tanks

Double-wall steel tank with interstitial monitoring, 2-hour fire rated.

Capacity
On request
Standard
UL 142, AS 1692
Compatible media
Fuels, with separate compartments for multiple grades

Common questions

Can’t see yours? Call NSW +61 2 4964 8270 or WA +61 8 9434 1707.

A tank inside a tank. The primary wall holds the fuel and a secondary wall surrounds it. If the primary wall ever leaks, the outer wall holds the fuel in the interstitial space between the walls instead of letting it reach soil or groundwater.
Through the interstitial space. Double-wall FRP tanks use Truchek® hydrostatic monitoring, which fills that space with brine and watches its level in a reservoir on top of the tank. Glasteel® II tanks have a factory-fitted vacuum gauge on the interstitial space. Flameshield® 2-hour tanks also have interstitial monitoring.
AS 4897 calls for secondary containment, non-corroding tanks and pipework and overfill protection on underground petroleum storage systems, and state EPAs set the rules for each site. Our double-wall FRP and Glasteel® II tanks give that secondary containment, with monitoring of the interstitial space. This is general information, not legal advice.
No. On a self-bunded tank the integral wrap-style steel bund meets State and Territory regulatory requirements, so there are no earthen or concrete bunds to build and no rainwater collecting in an open bund.
Double-wall gives full secondary containment and interstitial monitoring, and is the usual choice for fuel. Where that isn’t needed, such as water or some AdBlue installs, a single-wall FRP tank is lighter and quicker to install.
Both give double-wall containment underground. A double-wall FRP tank is fibreglass inside and out, with Truchek® hydrostatic leak monitoring. Glasteel® II has a welded steel inner wall that carries the structural load and an FRP outer wall that fully encloses the steel, so the steel never touches soil or groundwater and needs no cathodic protection.

Send us your spec for a quote