Home / Calculators / Forecourt tank sizing
Forecourt tank sizing calculator
The tank capacity each fuel grade needs from what you sell or use a week and your delivery drop size, and how the grades fit into tanks.
Result
Send these figures to a sales engineer covering your state. We reply within 2 business days.
Send these specs for a quoteHow the calculator works
- Daily sales for each grade are your weekly litres divided by 7.
- Capacity for each grade is the safety stock (daily sales multiplied by the days you want left) plus one delivery drop, so a full drop still fits when the tank is down to its safety stock. If you enter a fill allowance, the capacity is raised so that space stays empty at the top. Each grade is rounded up to the next 1,000L, with a 2,000L minimum.
- Deliveries a week is weekly sales divided by the drop size. Days of stock when full is the usable capacity divided by daily sales.
- Underground tank layout fills tanks with the largest grade first, up to 150,000L and 4 compartments per tank, as published for our service station fuel tanks. A grade over 150,000L gets its own tanks, split evenly. AdBlue is shown as its own tank, though it can also be a compartment beside the diesel.
- Above-ground tank layout gives each grade its own self-bunded tank, up to 55,000L for petrol and 110,000L for diesel, and splits a grade evenly across tanks when it needs more.
This calculator is general information to help with early sizing. Your installer and the site's approvals set the final layout.